You are using an unsupported browser. Please update your browser to the latest version on or before July 31, 2020.
close
You are viewing the article in preview mode. It is not live at the moment.
Home > True Protection > Alarm Systems > Home Automation Equipment > Enroll and configure the Alarm.com Smart Thermostat
Enroll and configure the Alarm.com Smart Thermostat
print icon

​​​​​​Add or remove the Smart Thermostat

To add or remove the ADC-T3000:

If using a Z-Wave Security 2 (S2) and/or SmartStart-capable Z-Wave controller, see Add an S2-encrypted Z-Wave device or Add or remove a Z-Wave SmartStart-enabled device. If not, refer to the steps below:

  1. Put the Z-Wave controller into ADD mode. Refer to the controller documentation for more information.
  2. Press the Minus button.
  3. Select SETTINGS.
  4. Select NETWORK.
  5. Select ADD or REMOVE.
  6. Log into the Customer Website to sync the thermostat with the customer's account.
To add or remove the ADC-T2000:
  1. Put the security panel or hub in inclusion or deletion mode so that it can detect the Smart Thermostat. If unsure about how to do this, consult the instruction manual for the control device.
  2. Verify the Smart Thermostat is in off mode. To do this, press More on the right side of the thermostat until only the temperature display is lit. Neither the heat nor the cool icons should be lit on the thermostat. 
  3. To enroll the thermostat, press and hold Down until the Radio icon icon lights up. The radio icon pulses white when the Smart Thermostat is being added into a Z-Wave network, and pulses red when removed.

 

Configure the Smart Thermostat

Once the Smart Thermostat is enrolled into the Alarm.com Z-Wave network, it can be fully configured using the Partner Portal, MobileTech app, Customer Website, or app. The HVAC system type can also be configured locally using the thermostat. 

Note: The setup wizard for the ADC-T2000 can be removed from or restored to the Customer Website and app. For more information, see Remove or restore the setup wizard for the ADC-T2000.

 

To configure the Smart Thermostat using the Customer Website:

Note: This option does not appear if thermostat configuration is not enabled for customers.

  1. Log into the Customer Website.
  2. In the Thermostats card, click Details.
  3. Click Advanced Configuration.
  4. Configure the thermostat as desired. For more information about the settings, see Settings
  5. Click Save

The Smart Thermostat automatically configures to Celsius or Fahrenheit based on the customer account settings. For more information about how to change this, see How do I change the display unit on the Smart Thermostat to Celsius or Fahrenheit?.

To configure the Smart Thermostat using the Customer app:

Note: This option does not appear if thermostat configuration is not enabled for customers.

  1. Log into the Customer app.
  2. In the Thermostats card, tap Details.
  3. Tap Configure.
  4. Tap Device Settings.
  5. Configure the thermostat as desired. For more information about the settings, see Settings
  6. Tap Apply
To configure the Smart Thermostat's system type locally using the thermostat:
ADC-T3000

The local installer settings can be accessed at any time.

  1. Press the Minus button.
  2. Select SETTINGS.
  3. Select INSTALLER.
  4. Select CONTINUE.
  5. The following settings can be selected:
    • Z1: Reconfigure the Z1 terminal to NONEW3HUMIDDEHUMID, or VENT.
    • Z2: Reconfigure the Z2 terminal to NONEW3HUMIDDEHUMID, or VENT.
    • RECONFIG: Reset the automatically detected wiring settings.
    • RESET: Factory reset the thermostat.
ADC-T2000

Note: The ADC-T2000 can only be configured locally with the most common configurations for the HVAC system type. It does not include custom configurations (e.g., O/B terminal selection, humidifier, etc.), or settings found in the User or Advanced tabs on the Partner Portal and MobileTech app. 

  1. Verify the Smart Thermostat is in off mode. To do this, press and hold More on the thermostat until only the temperature display is lit. Neither the heat nor the cool icons should be lit on the thermostat. 
  2. Press and hold Up for five seconds until the display shows a version number.
    • Z-Wave Icon: Radio firmware (Always 1.10)
    • Heat and Cool Icons: Programming firmware - This must be displayed to get to Configuration.
  3. Press and hold Up again for five seconds until the display shows the HVAC setup. This displays current configuration first.
  4. Press Up or Down to select the thermostat configuration. The configuration depends on the Smart Thermostat's firmware version. For descriptions about the thermostat configuration, see the following table that applies to the user's thermostat version. 
  5. Press More to confirm the selection.

Note: If the process times out, it is required to start over from step 2.

Firmware 1.50

Configuration System Type Description/Notes
NORM Normal 2-Heat 2-Cool System Normal electric system, thermostat turns on fan with heat. Two or fewer stages of heating and cooling are allowed.  
FOSL Fossil 2-Heat 2-Cool System (for hydronic with heat w/ no fan) Normal fossil heating system, thermostat does not turn on fan using G wire when heating. Gas furnace or Hydronic usually.
PUMP Heat pump (O terminal) Heat pump using the O in O/B terminal with two or fewer stages of electric Aux heating.
PMPB Heat pump (B terminal) Heat pump using the B in O/B terminal with two or fewer stages of electric Aux heating.
DUAL Dual fuel system (O terminal) Heat pump with two or fewer stages of Fossil Aux heating using the O in O/B terminal.
DULB Dual fuel system (B terminal) Heat pump with two or fewer stages of Fossil Aux heating using the B in O/B terminal.

Firmware 1.30

Configuration System Type Description/Notes
NORM Normal 2-Heat 2-Cool System Normal electric system, thermostat turns on fan with heat. Two or fewer stages of heating and cooling are allowed.  
FOSL Fossil 2-Heat 2-Cool System (for hydronic with heat w/ no fan) Normal fossil heating system, thermostat does not turn on fan using G wire when heating. Gas furnace or Hydronic usually.
PUMP Heat pump (O terminal) 2-stage heat pump using the O in O/B terminal with two or fewer stages of electric Aux heating.
PMPB Heat pump (B terminal) 2-stage heat pump using the B in O/B terminal with two or fewer stages of electric Aux heating.
DUAL Dual fuel system (O terminal) 2-stage heat pump with two or fewer stages of Fossil Aux heating using the O in O/B terminal.
DULB Dual fuel system (B terminal) 2-stage heat pump with two or fewer stages of Fossil Aux heating using the B in O/B terminal.

Firmware 1.20 or older

Note: The number of stages cannot be changed locally and is the reason why it is recommended to configure 1.20 via MobileTech or the Partner Portal.

Configuration System Type Description/Notes
C2H2 Normal 2-Heat 2-Cool System Normal electric system, thermostat turns on fan with heat. Two or fewer stages of heating and cooling are allowed.
P2H2 Heat pump (O terminal) 2-stage heat pump using the O in O/B terminal with two or fewer stages of electric Aux heating.

Settings

User settings

These settings are basic things within the thermostat concerned with preference and user interaction. They involve the lockout local changes, temperature limits, and how the thermostat responds to heating/cooling needs.

  • Display ON (ADC-T2000 only): The thermostat mode and temperature is displayed at all times when this feature is enabled. (1.5 FW+ only)
  • Display Options (ADC-T3000 only): Adjust what the thermostat displays on the main screen.
    • Simple mode just displays the current temperature along with the mode (e.g., cooling, heating, auto) and setpoint.
    • Humidity mode displays the current humidity percentage below the temperature.

      Note: Humidity display is not supported when in Celsius mode.
       
  • Heat/Cool Setpoint: The allowed range for the Target Temps in Heat and Cool modes.
  • Overshoot: The number of degrees beyond the Target Temp the system heats or cools before shutting off. (Recommend leaving this at 0 for comfort and efficiency reasons)
  • Swing: The number of degrees, above and below the Target Temp, the HVAC system comes on to cool or heat, preventing wear on the system components due to excessive cycles.
  • Thermostat Lock:
    • Partial: Allows Temp Changes but not Mode. This functionally disables the mode button.
    • Enabled: Locks all local changes. This disables all buttons, so even if it's in off mode the user is not able to locally check the firmware version.
  • Motion Sensor (ADC-T3000 only):
    • This setting will enable the thermostat screen to wake when motion is detected nearby.
    • This feature is only available if the thermostat is AC powered.
Advanced settings

These settings involve how the thermostat runs the various heating and cooling cycles.

Important: Leave proper delays and off times to prevent the system from overheating or causing unnecessary wear and tear.

  • Balance Point: The outdoor temperature at which the heat pump stops running and only use Aux heat.
  • Calibration Temperature: Used to adjust the ambient room temperature reading up or down to a more accurate value. This may be necessary if the thermostat is installed in a location with abnormal temperature conditions, such as in direct sunlight or on a wall adjacent to an unheated room.
  • Cooling Differential: The number of degrees above the Target Temp the Ambient Temp can raise before activating the next stay of cooling. This works in conjunction with Staging Delay.
  • Compressor Delay: The amount of time the compressor waits to turn on to prevent damage from excessive cycling. Each time the compressor is turned on, the pressure is built inside. This pressure must be equalized once it is turned off before it can be cycled on again.
  • Fan Circulation Period: The amount of time the fan is in circulation. This feature works with Fan Duty Cycle to determine how long the fan is on during this time.
  • Fan Duty Cycle: The percentage of the circulation period the fan is on. For example, if the circulation time is 20 minutes, and the duty cycle is 25%, the fan is on for 5 minutes, then off for 15 minutes until the next cycle.
  • Enable Fan ON Control: When enabled, allows the customer to select 'Indefinite' under fan options through the thermostat UI. This runs the fan continuously until deactivated.
  • Fan Purge: The amount of time the fan remains on to clear the air ducts after the system is turned off. It's a good idea to keep this around 1 minute or higher in order to ensure any leftover warm or cold air is moved into the house and not wasted.
  • Heat/Cool Staging Delay: The amount of time the heating or cooling activates the next stage of heating or cooling if the setpoint has not been reached.
  • Heating Differential: The number of degrees below the Target Temp the Ambient Temp can drop before activating the next stage of heating. This works in conjunction with Staging Delay.
  • Heat Pump Expiration: Amount of time the heat pump runs for without reaching the target setpoint.
  • Humidity Differential: The number of degrees below the Temperature Setpoint that the AC is allowed to cool in order to reduce humidity to the desired setpoint. For example, if the temperature setpoint is 72˚F, the Humidity Setpoint is 80%, and the Humidity Differential is 3˚F and it is currently 72˚F with a humidity of 90%, the AC will continue to run until either the humidity reaches 80% or the temperature reaches 69˚F.
  • Humidify While Heating (ADC-T3000 only): When enabled, the humidifier will only run while the heat is also running when in heat or auto mode. When disabled, the humidifier will run any time the humidity levels drop below the humidity setpoint.
  • (Pump) Staging Delay: The amount of time allowed for the Ambient Temp to be above or below the Target Temp before the next heating or cooling stage kicks in. This works in conjunction with Heating and Cooling Differentials.
  • Recovery Setting: This determines how the system behaves if it has multiple stages. If it had to trigger a secondary stage to heat or cool the home as it gets closer to the target Economy turns off those stages and Comfort Keeps them on until the target is reached.
  • Run Fan with Aux Heat: If the system is a Heat Pump this determines if the G wire is active during Aux Heat. It is not advised to change this setting.
Installer settings

These determine how the thermostat controls the HVAC system.

Caution: Making incorrect changes to these settings can cause catastrophic system failures.

  • Cool Stages: Determines the number of condenser stages the system has.
  • Configurable Z Terminals:
    • W3 (Normal: 3rd stage heat, Heat Pump: 3rd Aux Stage)
    • Humidity
    • O/B Zoning (Normal: Master thermostat control, Heat Pump: O and B both used with B going into the Z terminal)
  • Heat Type:
    • Electric is used for heating systems that require the thermostat to turn on the fan.
      • Examples: Forced Air Heating Systems, generally any electric based heating sources, most Heat Pumps
    • Fossil (e.g. gas, oil) is used for heating systems that don't require the thermostat to turn on the fan. This is a little misleading since this is not strictly for fossil fuel powered systems, but the terminology is industry standard. 
      • Examples: Hydronic heating (radiators), baseboard heating, Dual Fuel heat pumps, any furnace that turns on the fan without relying on the thermostat (common with fossil fuel furnaces that have a heating delay built in so that the system doesn't blow around cold air at first), Radiant floor heating
  • Heat/Cool Stages: Determines the number of heat stages present in the house for Normal. For Heat Pump, it is the number of Aux/Emergency stages.
  • Heat Pump/Aux Stages: Determines the number of pump and auxiliary heat stages present on the system.
  • HVAC Type: This primarily determines how the thermostat distributes calls for heat.
  • O/B Terminal:
    • Normal: Master thermostat control
    • Heat Pump: O and B wire Selection
  • Wiring Configuration: Displays any available wiring configuration information.

Remove or restore the setup wizard for the ADC-T2000

The setup wizard is available using the Customer Website or app after the thermostat has been enrolled in the Z-Wave network. The wizard allows the user to select the wires that are connected and configure the settings for the thermostat. The setup wizard for the ADC-T2000 can be removed from and restored to the Customer Website and app using the Partner Portal or MobileTech app.

 

Frequently asked questions

Is an Alarm.com account required to use the Smart Thermostat? 

An Alarm.com account is required to configure the ADC-T2000 for the first time. Initial configuration can be done through the customer wizard either on the Alarm.com Customer Website or app. The ADC-T3000 can configure additional options locally. This can also be done on the Partner Portal or MobileTech app.

If a customer later cancels service, the Smart Thermostat continues to function, and the customer retains basic control of heat and cool modes as well as the target temperature. However, all advanced features and capabilities (such as Smart Thermostat scheduling and Away from Home overrides) is lost. 

Which settings can be changed on the Customer Website?

Only the Basic settings are accessible through the Customer Website. All other settings can be modified using the Partner Portal.

The first time a customer logs in through the Customer Website after a thermostat is installed, they'll be shown an installation wizard which will allow them to select their HVAC type and wires, which automatically configures the Installer settings for them.

How does the user set up thermostat schedules? 

Thermostat schedules are set up using either the Customer Website or app. For more information about setting up thermostat schedules, see Configure Thermostat Schedules

The heat pump heats when it’s supposed to be cooling. Why is this happening?

Heat pumps have either an O terminal or a B terminal. When configuring the Smart Thermostat, it prompts to select which terminal type the heat pump has. If the system heats when it’s supposed to be cooling, this means that the incorrect terminal type was selected at configuration.

This setting can be updated when configuring the device using either the Partner Portal or MobileTech app in the Installer tab. When Heat Pump is selected as the HVAC Type, the option to select the O or B terminal appears on the configuration page. 

Why aren't all the settings visible on every system?

Depending on the HVAC system, not all settings are needed. This is why configuring the Installer settings correctly is very important. Those settings determine what options are shown on the other pages.

Feedback
0 out of 0 found this helpful

Attachments

Enroll_and_configure_the_Alarm.com_Smart_Thermostat.pdf
scroll to top icon