Smart Thermostat Installation, Wiring & Setup
Safety First — Turn OFF power to HVAC at the circuit breaker before installing or servicing. Leave power off until installation is complete. Do not short furnace/AC terminals to test. Follow local codes. Use only two AAA alkaline batteries or a listed Class 2 24 VAC supply. Do not use on high-voltage (120/240 V) systems—contact an HVAC professional.
Box Contents & Recommended Tools
In the box
- ADC-T3000 thermostat
- User guide
- Drywall anchors & screws (x3)
- Wire labels
- Batteries (2× AAA recommended; device supports 2× AAA)
Recommended tools
- Small flat/Phillips screwdriver
- Drill & 3/16” bit (for anchors)
- Level (bubble on back plate provided)
- Phone for wire photo & account setup
- Multimeter (verify 24 VAC)
Thermostat Overview
Buttons
Icon | Function |
---|---|
MENU | Change mode, fan, settings, features |
UP / DOWN | Adjust setpoint / navigate |
SELECT | Confirm menu selections |
Modes
- HEAT — heat only
- COOL — cool only
- AUTO — auto heat/cool
- EMER — heat-pump aux/emergency heat
- OFF — system off
Display indicators
- HEATING / COOLING — call status
- Temperature sensor icon — using Alarm.com Temperature Sensor(s)
Best location
- Interior wall ~5 ft (1.5 m) high, good airflow
- Avoid sun, drafts, appliances, supply/return vents
- Avoid damp areas; finish construction/painting first
Preparation
- Test existing system from old thermostat (do not short terminals).
- Turn power OFF at HVAC breakers.
- Remove old thermostat cover (leave wires connected), label and photograph wiring, then disconnect & secure wires so they don’t fall into wall.
- Verify 24 VAC system (18–24 AWG conductors; ~¼″ stripped, straight).
Mount Back Plate
- Use built-in bubble level; mark holes.
- (Optional) Install trim plate first to cover old marks.
- Drill 3/16″, set anchors, and fasten back plate.
Wiring
Caution: If extra/unidentified wires exist, do not land them—contact an HVAC professional. Confirm 24 VAC only. If your system has separate RC and RH wires, no jumper is needed. If you have a single R, land on RC or RH and select that terminal during setup (digital jumper is created).
Conventional Systems
Terminal | Description |
---|---|
RC / RH | Cooling / Heating power |
Z1 / Z2 | Configurable: W3, H (humidifier), DH (dehumidifier), EX (ventilation) |
W / W2 | Heat stages 1 / 2 |
Y / Y2 | Cool stages 1 / 2 |
G | Fan |
O / B | Cool/Heat energized reversing valve (as applicable) |
C | Common (secondary of transformer) |
Heat Pump Systems
Terminal | Description |
---|---|
RC / RH | Cooling / Heating power |
Z1 / Z2 | W3, H, DH, EX |
W / W2 | Aux/backup heat stages 1 / 2 |
Y / Y2 | Compressor stages 1 / 2 |
G | Fan |
O / B | Reversing valve (energized in COOL = O, in HEAT = B) |
C | Common |
Two-wire hydronic heat: install the included power resistor between C and W at the equipment (not at thermostat) if prompted.
Power & Batteries
- Power via 24 VAC C-wire or two AAA alkaline batteries (batteries recommended as backup).
- If using a wall transformer, connect between C and RH for heat-only or cool-only systems, with jumper removed to the unused R.
- Battery warnings: Replace at first “LOW BATTERY” alert; yearly as preventive; immediately if buttons flash amber with no screen. Always use new alkaline cells.
Attach Thermostat
- Tuck excess wire into wall; align pins carefully.
- Press thermostat body firmly onto back plate (flush fit).
Restore Power & Guided Setup
- Turn breakers back on.
- Follow on-screen prompts; auto-detect wiring.
Heat type: Electric (fan on by stat) vs Fossil (fan by furnace). Backup heat: Electric vs Dual Fuel. Z1/Z2: assign W3/H/DH/EX as needed.
Z-Wave Enrollment
- Put the Z-Wave controller in Add mode.
- On thermostat: MENU → SETTINGS → NETWORK → ADD.
- S2 controllers: enroll as S2; enter the first five DSK digits when prompted.
- Sync to customer account via the website/app after inclusion.
Configure Features
User Preferences
- °F/°C: MENU → SETTINGS → USER → F/C
- Motion-wake (AC-powered only): … USER → MOTION → ON
- Disable AUTO: … USER → AUTO → DISABLE
Humidity Control
- Mode: … USER → HUMIDITY → MODE (OFF/DEHUMID/HUMID/AUTO)
- Setpoints: … USER → HUMIDITY → SETPOINT → HUMID / DEHUMID (20% deadband enforced)
- Use Z1/Z2 for external humidifier/dehumidifier; without external dehumidifier, cooling cycles may extend to dehumidify.
Ventilation
Configure HRV/ERV/air baffle via Z1/Z2. Default: 15 min/hr. Adjust advanced settings online.
Reconfigure HVAC
MENU → SETTINGS → INSTALLER → RECONFIG to re-run setup without removing Z-Wave.
Operation
- Wake: press any button. Mode/setpoint: MENU → MODE, then ▲/▼.
- Fan: MENU → FAN MODE (AUTO/ON/CIRCULATE).
- Emergency heat (heat pumps): select EMER under mode.
System Check (Mild Weather Recommended)
Heating
- MODE → HEAT
- Raise setpoint; wait up to 5 min for call.
Cooling
- MODE → COOL
- Lower setpoint; wait up to 5 min for call.
Troubleshooting
- No heat/cool when expected — Increase delta ≥2°, wait 5 min (compressor delay). If still off, contact HVAC.
- Heat pump heats/cools backwards — Move reversing valve wire between O ↔ B and reconfigure.
- Buttons flash amber; screen dark — Batteries critically low; replace immediately.
- Auto wire-detect incorrect — Bypass: MENU → SETTINGS → INSTALLER → CONTINUE → RECONFIG → YES, choose RC/RH, then Check Wiring and Reinstall → BYPASS and configure manually.
- Safety Delay / System Protect — Built-in anti-short-cycle. Frequent delays: move R from RH to RC for cooling, or add isolation relay (e.g., 24 V fan/compressor relay). If persistent, consult HVAC.
- Power Resistor Required — Install 1 kΩ, ½ W across hydronic valve terminals (e.g., Taco 1 & 2) at equipment.
- Isolation relay required — Overcurrent detected on W/Y/G; isolate with a 24 V coil relay and re-test.
- Z-Wave repeater inactive — Thermostat repeats only if added to network while powered by common (C). Remove & re-add after connecting C.
Network Management
- Remove from Z-Wave: Controller in Remove mode → MENU → SETTINGS → NETWORK → REMOVE.
- Factory Reset: MENU → SETTINGS → INSTALLER → RESET (removes Z-Wave & clears all settings). Best practice: remove from network first, then reset.
Notices
FCC: This device complies with Part 15. Operation is subject to (1) this device may not cause harmful interference; (2) this device must accept any interference received. Class B compliance statement applies.
IC: Operation per Industry Canada rules; use approved antenna types/gain to limit e.i.r.p.
Z-Wave: Operates with certified Z-Wave devices; non-battery nodes act as repeaters. Unauthorized modifications void authority to operate.